Published Papers
     Search Papers (Springer,
   After 2008)
     Search Papers (Dbpia,
   Until 2007)
     Search Papers (JMST
   own data base)
       - Classification By Year   
       - Classification By Topic
     Special Issues
   
           
   
 
 
Subject Keyword Abstract Author
 
 
Experiment on the performance improvement of air-to-air heat pump adopting the hot gas bypass method by outdoor fan speed variation

Jinho Lee/Ju-Suk Byun
The Journal of Mechanical Science and Technology, vol. 23, no. 12, pp.3407-3415, 2009

Abstract : This study focuses on the effect of outdoor coil fan speed on the performance variation of the heat pump system by adopting the hot gas bypass method, and on the performance improvement with hot gas bypassing using the time step method to defrost. Tests were conducted for fan speeds 90, 60 and 30% of the normal speed of the outdoor coil together with the stationary case. Performance of the heat pump is compared with the conventional time step defrosting method for coefficient of performance (COP) and total heat capacity. Results show that the integrated heating capacity with hot gas bypassing is highest at 60% (780 rpm) of the fan speed and is 8.6% higher than that of the time step defrosting method. The averaged COP of the heat pump in this case is higher by 3.8% than the time step defrosting method and 2.8% higher than that of the stationary fan.

Keyword : Heat pump; Frost; Hot gas bypass; Fan speed; COP; Heating capacity

 
 
 
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org