Thermal performance analysis of heat exchanger for closed wet cooling tower using heat and mass transfer analogy
Seong-Yeon Yoo/Jin-Hyuck Kim/Kyu-Hyun Han
The Journal of Mechanical Science and Technology, vol. 24, no. 4, pp.893-898, 2010
Abstract : In closed wet cooling towers, the heat transfer between the air and external tube surfaces can be composed of the sensible heat transfer
and the latent heat transfer. The heat transfer coefficient can be obtained from the equation for external heat transfer of tube banks. According
to experimental data, the mass transfer coefficient was affected by the air velocity and spray water flow rate. This study provides
the correlation equation for mass transfer coefficient based on the analogy of the heat and mass transfer and the experimental data. The
results from this correlation equation showed fairly good agreement with experimental data. The cooling capacity and thermal efficiency
of the closed wet cooling tower were calculated from the correlation equation to analyze the performance of heat exchanger for the tower.
Keyword : Closed wet cooling tower; Heat and mass transfer analogy; Heat and mass transfer coefficients; Heat exchanger |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org |
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org |
|
|
|
|