The effect of PSD on life safety in subway station fire
Jae Seong Roh/Hong Sun Ryou/Sung Wook Yoon
The Journal of Mechanical Science and Technology, vol. 24, no. 4, pp.937-942, 2010
Abstract : Fire is a major risk in the event of subway station fire due to the confining geometry of the underground space. As a part of an effort to
improve the life safety in subway fire, the platform screen door (PSD) is more and more installed on the ground that PSD provides many
benefits to passenger¡¯s safety. This paper not only performs fire simulation and evacuation modeling but also estimates the effect of PSD
on passenger¡¯s life safety and an evacuation measure in the event of a subway station fire. The Fire Dynamics Simulator (FDS V406)
code is used to predict smoke spread and the time available for evacuation during the fire. The time required for evacuation is obtained
from simple travel time relationship from Nelson and MacLennan. The passengers in platform with PSD have more available time of
about 100s than in case without PSD. The subway turnstiles (ticket gate) dramatically increase the time required for evacuation due to
jam and bring on danger passenger¡¯s life safety. Therefore, the passage without barriers like turnstiles will be required not to obstruct
evacuation for passengers in an emergency case of subway fire.
Keyword : Available safe egress time (ASET); Life safety; Platform screen door (PSD); Required safe egress time (RSET); Subway station fire |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org |
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org |
|
|
|
|