Experimental measurement and numerical computation of the air side convective heat transfer coefficients in a plate fin-tube heat exchanger Jin Gi Paeng
The Journal of Mechanical Science and Technology, vol. 23, no. 2, pp.536-543, 2009
Abstract : The air-side forced convective heat transfer of a plate fin-tube heat exchanger is investigated by experimental measurement
and numerical computation. The heat exchanger consists of a staggered arrangement of refrigerant pipes with
a diameter of 10.2 mm and a fin pitch of 3.5 mm. In the experimental study, the forced convective heat transfer was
measured at Reynolds numbers of 1082, 1397, 1486, 1591 and 1649 based on the diameter of the refrigerant piping and
on the maximum velocity. The average Nusselt number for the convective heat transfer coefficient was also computed
for the same Reynolds number by using the commercial software STAR-CD with the standard k −¥å turbulent model.
It was found that the relative errors of the average Nusselt numbers between the experimental and numerical data were
less than 6 percent in a Reynolds number range of 1082~1649. The errors between the experiment and other correlations
from literature ranged from 7% to 32.4%. However, the literature correlation of Kim et al. is closest to the experimental
data within a relative error of 7%.
Keyword :
Air-side convective heat transfer; Plate fine-tube heat exchanger; Average Nusselt number
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org |
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org |
|
|
|
|