|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bypass line assisted start-up of a loop heat pipe with a flat evaporator Joon Hong Boo
The Journal of Mechanical Science and Technology, vol. 23, no. 6, pp.1613-1619, 2009
Abstract : Loop heat pipes often experience start-up problems especially under low thermal loads. A bypass line was installed
between the evaporator and the liquid reservoir to alleviate the difficulties associated with start-up of a loop heat pipe
with flat evaporator. The evaporator and condenser had dimensions of 40 mm (W) by 50 mm (L). The wall and tube
materials were stainless steel and the working fluid was methanol. Axial grooves were provided in the flat evaporator
to serve as vapor passages. The inner diameters of liquid and vapor transport lines were 2 mm and 4 mm, respectively,
and the length of the two lines was 0.5 m each. The thermal load range was up to 130 W for horizontal alignment with
the condenser temperature of 10¡ÆC. The experimental results showed that the minimum thermal load for start-up was
lowered by 37% when the bypass line was employed.
Keyword :
Loop heat pipe; Flat evaporator; Start-up; Bypass line
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org |
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org |
|
|
|
|