Characteristics of the Cooling Water Fouling in a Heat Exchanging System Sun-Kyung Sung
The Journal of Mechanical Science and Technology, vol. 22, no. 8, pp.1568-1575, 2008
Abstract : This study investigated the efficiency of the physical water treatment method in preventing and controlling fouling
accumulation on heat transfer surfaces in a laboratory heat exchange system with tap and artificial water. To investigate
the fouling characteristics, an experimental test facility with a plate type heat exchange system was newly built, where
cooling and hot water moved in opposite directions forming a counter-flow heat exchanger. The obtained fouling resistances
were used to analyze the effects of the physical water treatment on fouling mitigation. Furthermore, the surface
tension and pH values of water were also measured. This study compared the fouling characteristics of cooling water in
the heat exchange system with and without the mitigation methods for various inlet velocities. In the presence of the
electrode devices with a velocity of 0.5m/s, the fouling resistance was reduced by 79% compared to that in the absence
of electrode devices.
Keyword :
Fouling; Fouling factor; Precipitation fouling; Physical water treatment; Heat exchange system; Anti-fouling technology
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JMST Editorial Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-3605, E-mail: editorial@j-mst.org |
JMST Production Office: #702 KSTC New Bldg, 22 7-gil, Teheran-ro, Gangnam-gu, Seoul 06130, Korea
TEL: +82-2-501-6056, FAX: +82-2-501-3649, E-mail: editorial@j-mst.org |
|
|
|
|